AFT Cargo-Compartment Fan Fault A320

1. Possible Causes:

-CONT-AIR COND SYSTEM 1 (47HH)

-wiring

2. Job Set-up Information

A. Referenced Information

Ref. AMM 21-61-00-710-001 Operational Test of the Pack Temperature-Control System

Ref. AMM 21-61-34-000-002 Removal of the Air-Conditioning System Controller

Ref. AMM 21-61-34-400-002 Installation of the Air-Conditioning System Controller

Ref. ASM 21-63-03

3.Fault Confirmation

SUBTASK 21-28-00-710-053-A

A. Test

NOTE:  This fault isolation procedure is applicable although the AFT cargo-compartment ventilation system is not installed.

(1) Do the operational test of the pack temperature-control system Ref. AMM 21-61-00-710-001.

4. Fault Isolation

SUBTASK 21-28-00-810-067-C

A. If the test gives the maintenance message FWD CARGO FAN OR SPLY:

-replace the CONT-AIR COND SYSTEM 1 (47HH) Ref. AMM 21-61-34-000-002 and Ref. AMM 21-61-34-400-002.

(1)If the fault continues:

(a)Remove the CONT-AIR COND SYSTEM 1 (47HH) Ref. AMM 21-61-34-000-002.

(b)Do a check and repair the wiring between:

-connector (47HH/AB) pin 4K and GND Ref. ASM 21-63-03.

(c) Install the CONT-AIR COND SYSTEM 1 (47HH) Ref. AMM 21-61-34-400-002.

SUBTASK 21-28-00-710-062-A

B. Do the test given in Para. 3.

Read me first

All instructions and limitations given in those documents that relate to the resetting of systems both on the ground and in the air must be respected. No reset should be attempted without a thorough appreciation of the technical ramifications. No more than one computer should be reset at any one time. No reset should be attempted in flight unless specifically permitted by the QRH. Maintenance messages remaining after a reset require engineering investigation.